Difference between revisions of "Energy storage sizing and selection"

From Open Source Solar Project
Jump to navigation Jump to search
Line 9: Line 9:
 
*A system that is in a difficult o access location may warrant a more conservative value.
 
*A system that is in a difficult o access location may warrant a more conservative value.
  
'''Step 2: Determine days of autonomy paremeter'''
+
'''Step 2: Determine days of autonomy parameter'''
  
 
The days of autonomy parameter determines the number of days that the system will be able to meet energy needs without additional charging. 1 day of autonomy provides enough energy storage capacity to provide energy for the loads from the [[Load evaluation|load evaluation]] for 1 day without any additional charging. Each additional day adds an additional day of energy storage capacity. For example:
 
The days of autonomy parameter determines the number of days that the system will be able to meet energy needs without additional charging. 1 day of autonomy provides enough energy storage capacity to provide energy for the loads from the [[Load evaluation|load evaluation]] for 1 day without any additional charging. Each additional day adds an additional day of energy storage capacity. For example:

Revision as of 09:51, 25 November 2020

A flowchart depicting the priamry inputs and outputs of the energy storage sizing and selection process.

The energy storage system is sized based upon the average daily energy requirements for the system and several key parameters. The first 5 steps of this process output a suggest Ah size for the energy storage system, but then it is necessary to determine a series and parallel configuration based upon the available battery voltages and sizes.

Step 1: Determine depth of discharge parameter

The depth of discharge parameter determines the percentage of the energy storage system that be considered usable for the system design. The depth of discharge value chosen affects the capacity, cycle life, and cost of the energy storage system. Lead acid batteries are not tolerant of regular deep discharges, thus values between .4-.5 (40-50%) are typically used. A value of .5 is often cited as providing the highest number of cycles relative to cost, but there are additional considerations that should go into determing the Depth of discharge value:

  • A system that is anticipated to be used heavily may warrant a more conservative value.
  • A system that is in a difficult o access location may warrant a more conservative value.

Step 2: Determine days of autonomy parameter

The days of autonomy parameter determines the number of days that the system will be able to meet energy needs without additional charging. 1 day of autonomy provides enough energy storage capacity to provide energy for the loads from the load evaluation for 1 day without any additional charging. Each additional day adds an additional day of energy storage capacity. For example:

  • 205 Ah lead acid battery system x 1 day of autonomy = 205 Ah
  • 205 Ah lead acid battery x 2 days of autonomy = 410 Ah
  • 205 Ah lead acid battery x 3 days of autonomy = 615 Ah

The value that is chosen for this parameter depends largely upon the variability of the solar resource, the intended use of the system, and the budget. It is almost always preferable to have additional storage, therefore budget often becomes the primary constraint. There are various considerations that go into determining the value that is appropriate for a particular design:

  • If a system is intended for a location where the weather or solar resource is highly variable, the value for days of autonomy should be increased. It is possible using Weather and solar resource data sources to examine how frequently bouts of bad weather occur and their duration in any given location.
  • If a system is intended to power at a location where the users can will adjust their energy consumption according to the weather or that is used infrequently, fewer days of autonomy can be built into the system. A value of 2 days of autonomy may be appropriate in these cases as long as there is a sufficiently sized PV source or an additional form of generation.
  • If a system is intended to provide power at a location that must operate continually, like at a health clinic, it is recommended that a significant number of days of autonomy are build into the system or that an additional form of generation, like a generator, is added to the system. An energy storage system with 5-7 days of autonomy for a health clinic will often be quite substantial in size, difficult to charge properly, and costly. Therefore, a backup generator should be considered in this case.
  • The days of autonomy value that is chosen will be size the energy storage system to meet energy demand when the battery bank is new, but the storage capacity of the energy storage system will gradually decline over time. Therefore oversizing a battery bank to take this into account is a good idea.

Step 3: Determine battery temperature correction factor The temperature of lead acid batteries has a significant effect upon performance. When lead acid batteries reach a temperature below 25°C, their usable capacity begins to decline. This can lead to batteries being deeply discharged and damaged, therefore the size of the energy storage system should be adjusted to ensure that there is adequate energy available at the minimum expected indoor temperature for the location. Correction factors for various battery types:[1]

Temperature FLA AGM Gel
25°C 1.00 1.00 1.00
10°C 1.19 1.08 1.11
0°C 1.39 1.20 1.25
-10°C 1.70 1.35 1.42

Step 4: Calculate total Ah required

Total Ah required = average daily Watt-hours required ÷ system voltage parameter × battery temperature correction factor (step 3) × days of autonomy parameter (step 2) ÷ depth of discharge parameter (step 1)

Step 5: Calculate number of batteries in series

Lead acid batteries are commonly available in 2V, 4V, 6V, 12V designs that can be wired in series to achieve a 12V, 24V, or 48V system voltage. See Battery wiring for more information on how to properly configure a battery bank. With small systems 12V batteries are the standard, but as system size increases lower battery voltages lead to more storage with fewer parallel strings, which is a better design. Deep cycle batteries with voltages below 12V can be difficult to find in some locations.

Batteries in series = system voltage parameter ÷ chosen battery voltage

Step 6: Calculate number of batteries in series

Lead acid batteries are available in a variety of Ah ratings. They can be wired in parallel to achieve the desired total Ah of storage for the system. See Battery wiring for more information on how to properly configure a battery bank. The result of this calculation should be rounded up, meaning that if the number of parallel strings is more than 1, then 2 parallel strings are required. The other option would be to use a battery with a higher Ah rating.

Batteries in parallel = total Ah required (step 4) ÷ chosen battery Ah rating

Step 7: Calculate final Ah capacity

The final Ah capacity of the battery bank is the chosen battery Ah rating multiplied by the number of parallel strings. This value is important for other calculations in the design process.

Final Ah capacity = number of batteries in parallel (step 7) × chosen battery Ah rating

Notes/references

  1. Trojan Battery Company - Battery Sizing Guidelines https://www.trojanbattery.com/pdf/TRJN0168_BattSizeGuideFL.pdf